Hotline:010-62132998
Drive Systems
Ventilation System
Curtain System
Cooling System
Climate Controller
Download

Static pressure controller

Product Manual| Technical Parameters| Accessories| Application| After Sales Service

Automatic pressure-based control


Programmable On and Off durations for the open and close relays

1 to 900 seconds (up to 15 minutes)


Programmable Set point and Idle band

0.010 to 0.250 inWC


Programmable high and low pressure alarms


Two curtain relays (one open, one close)


Differential pressure sensor


Alarm relay (for external alarm system)


Four-button keypad


Four-digit LED display


Programming and status LEDs


Manual override and test modes

Power-failure settings protection


Incoming power

85 to 264 VAC, 50/60 Hz


Open/close relays

15 A at 120/230 VAC, resistive load

1/2 HP at 120 VAC, 1 HP at 230 VAC


Alarm relay

0.4 A at 125 VAC, 2.0 A at 30 VDC, resistive load

0.2 A at 125 VAC, 1.0 A at 30 VDC, inductive load


Sensor ratings


Pressure range 0 to 0.25 inWC


Output voltage 0 to 4 VDC


Supply voltage 11 to 30 VDC, 12 VDC typical


Supply current 30 mA


Operating range 32 to 185°F (0 to 70°C)


Storage range -40 to 194°F (-40 to 90°C)

Overpressure 20 psi